THERMOMETER, T5-600/62 MAX+/1AC II IR (Electrical Tester and Voltage Detector Kit)

This kit is designed to help electricians and HVAC technicians solve problems quicker. Test first for overheated electrical devices using an IR thermometer; then use electrical test tools to find out more about the problem.
Category:

Product Description

Features

Fluke T5 Voltage, Continuity and Current Testers.
  • Automatically measures volts ac and volts dc with precise digital resolution.
  • Displays resistance to 1000Ω.
  • Easy and accurate OpenJaw™ current measurement.
  • Continuity beeper.
  • Rugged enough to withstand a 10-foot (3m) drop.
  • 600V model.
  • Auto off mode to conserve battery life.
  • AC current.
  • Display hold.
  • All inputs of the T5-600 are protected to EN61010-1 CAT III 600V. UL, CSA and VDE listed.
Fluke 62 MAX+. Small in size. Big on toughness.
  • Dust and water-resistant: IP54 rated.
  • Rugged: 3-meter (9.8-foot) drop tested.
  • Ergonomically designed: Completely redesigned for a more natural hand fit.
  • Distance to spot: 12:1.
  • Dual lasers: Identifies area to be measured.
  • Large, backlit display: Makes data easier to read, even in dark areas.
  • C115 Deluxe soft carrying case with shoulder strap.

Specifications

Fluke T5-600 Voltage, Continuity and Current Tester
Specifications
Jaw opening
12.9 mm (0.5 in)
Max wire size
1/0 THHN Cable
Current range ac rms
0 to 100.0 A
Accuracy ac current (50/60 Hz)
3 % ± 3 counts
AC Response
Averaging
Voltage range ac
0 to 600 V
Accuracy ac voltage
1.5 % ± 2 counts
Voltage range dc
0 to 600 V
Accuracy dc voltage
1 % ± 1 count
Resistance range
0 to 1000 Ω
Continuity beeper threshold
On at <25 Ω, off at >400 Ω
Volts indicator LED threshold
Guaranteed on by 30 V ac
Environmental Specifications
Operating Temperature
-10 °C to 50 °C
Storage Temperature
-30 °C to 60 °C
Humidity (Without Condensation)
0 % to 95 % (5 °C to 30 °C); 0 % to 75 % (30 °C to 40 °C);
0 % to 45 % (40 °C to 50 °C)
Dust/water resistance
Yes
Operating Altitude
2000 meters max
Temperature Coefficient
0.1 x (specified accuracy)/°C (<18 °C or >28 °C)
Safety Specifications
Overvoltage category
CAT III 600 V ac/dc (EN61010-1)
Agency Approvals
UL, CSA, and VDE
Maximum voltage
Between any terminal and earth ground
Mechanical and General Specifications
Size
30.5 mm x 51 mm x 203 mm
Weight
300g
Warranty
Two-years
Battery Life
200 hour zinc chloride, 400 hour alkaline
Battery type
2 x AA
Low battery indicator
Yes
Current sensor opening
12.9 mm
Calibration cycle
1 year
Test leads
Type:
Heavy duty, flexible leads rated for 1000V use.
Field replaceable leads terminate in male shrouded banana plugs
Probes:
One red, one black.
Detachable Slim-Reach™ probe tips
Styles:
TP1 Slim Reach™ Test Probes
Safety Specifications
Safety
CAT IV 600 V, CAT III, 1000 V
Maximum voltage
1000 V AC rms from earth to ground, in compliance with EN61010
Fluke 62 MAX+ Infrared Thermometer
Specifications
Temperature Range
-30 °C to 650 °C (-22 °F to 1202 °F)
Accuracy
±1.0 °C or ±1.0% of reading, whichever is greater
-10 °C to 0 °C: ±2.0
-30 °C to -10 °C: ±3.0
Response Time (95%)
Fluke 62 MAX+
<300 ms (95% of reading)
Spectral Response
8 to 14 microns
Emissivity
0.10 to 1.00
Optical Resolution
12:1 (calculated at 90% energy)
Display Resolution
0.1 °C (0.2 °F)
Repeatability of Readings
±0.5% of reading or <±0.5 °C (1 °F), whichever is greater
Power
AA battery
Battery Life
8 hours with laser and backlight on
Physical Specifications
Weight
255 g (8.99 oz)
Size
(175 x 85 x 75) mm (6.88 x 3.34 x 2.95) inches
Operating Temperature
0 °C to 50 °C (32 °F to 122 °F)
Storage Temperature
-20 °C to 60 °C (-4 °F to 140 °F), (without battery)
Operating Humidity
10 % to 90 % RH non-condensing at 30 °C (86 °F)
Operating Altitude
2000 meters above mean sea level
Storage Altitude
12,000 meters above mean sea level
IP Rating
IP 54 per IEC 60529
Drop Test
3 meters
Vibration and Shock
IEC 68-2-6 2.5 g, 10 to 200 Hz, IEC 68-2-27, 50 g, 11 ms
EMC
EN 61326-1:2006 EN 61326-2:2006
Standards and Agency Approval
Compliance
EN/IEC 61010-1: 2001
Laser Safety
FDA and EN 60825-1 Class II

Models and Accessories

Model Name Description
Fluke T5-600/62 MAX+ Includes:

  • Fluke T5-600
  • Fluke 62 MAX+ IR Thermometer

 

Reviews

There are no reviews yet.

Be the first to review “THERMOMETER, T5-600/62 MAX+/1AC II IR (Electrical Tester and Voltage Detector Kit)”