Electrical Specifications
|
Maximum voltage to earth ground
|
1000 V
|
Battery type
|
AA alkaline IEC/EN LR6 (x4)
|
Battery life
|
More than 15 hours*
|
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off
|
Frequency range
|
40 Hz to 1 kHz
|
Ingress protection
|
IEC/EN 60529: IP30 with jaw closed
|
LCD
|
Digital reading
|
9999 counts
|
Refresh rate
|
4 per second
|
Operating temperature
|
-10 °C to + 50 °C
|
|
Storage temperature
|
-20 °C to + 60 °C
|
Operating humidity
|
Non condensing (<10 °C) (< 50 °F)
|
≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F])
|
≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F])
|
≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F])
|
(Non condensing)
|
Operating altitude
|
2000 m (6561 feet)
|
Storage altitude
|
12 000 m (39,370 feet)
|
Reference temperature
|
23 °C ±5 °C (73 °F ±9 °F)
|
Temperature coefficient
|
0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F])
|
Overload indication
|
OL
|
Data logging capacity
|
Minimum of 32,760 measurements
|
Data logging interval
|
1 second to 59 minutes and 59 seconds
|
Display reading specification with standard loop resistance
|
Input (Ω)
|
Minimum
|
Maximum
|
0.474
|
0.417
|
0.531
|
0.5
|
0.443
|
0.558
|
10
|
9.55
|
10.45
|
100
|
96
|
104
|
Safety
|
General
|
IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
|
Measurement
|
IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
|
Current clamp for leakage current measurements
|
IEC/EN 61557-13: Class 2, ≤30 A/m
|
Resistance to earth
|
IEC/EN 61557-5
|
Effectiveness of thepProtective measures
|
IEC/EN 61557-16
|
Electromagnetic compatibility (EMC)
|
International
|
IEC/EN 61326-1: Portable Electromagnetic Environment
|
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
|
Korea (KCC)
|
Class A equipment (Industrial Broadcast & Communications Equipment)
|
USA (FCC)
|
47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
|
Wireless Radio
|
Frequency range
|
2412 MHz to 2462 MHz
|
Output power
|
<10 mW
|
Radio frequency certification
|
FCC ID:T68-FBLE IC:6627A-FBLE
|
General Specifications
|
Conductor size
|
40 mm (1.57 in) approximately
|
Dimensions (L x W x H)
|
283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in)
|
Weight
|
880g (31 oz)
|
Warranty
|
One year
|
Earth Ground Loop Resistance
|
Range
|
Accuracy1 ± (% of reading + Ω)
|
0.025 Ω to 0.249 Ω
|
1.5% + 0.02 Ω
|
0.250 Ω to 0.999 Ω
|
1.5% + 0.05 Ω
|
1.000 Ω to 9.999 Ω
|
1.5% + 0.10 Ω
|
10.00 Ω to 49.99 Ω
|
1.5% + 0.30 Ω
|
50.00 Ω to 99.99 Ω
|
1.5% + 0.50 Ω
|
100.0 Ω to 199.9 Ω
|
3.0% + 1.0 Ω
|
200.0 Ω to 399.9 Ω
|
5.0% + 5.0 Ω
|
400 Ω to 599 Ω
|
10.0% + 10 Ω
|
600 Ω to 1500 Ω
|
20.00%
|
1 Loop resistance with no inductance, conductor centered and perpendicular to jaw
|
Earth ground leakage current mA
|
Autorange 50/60 Hz, True rms, crest factor CF ≤3
|
Range
|
Resolution
|
Accuracy1 ± (% of reading + mA)
|
0.200 mA to 3.999 mA
|
1 μA
|
2.0% + 0.05 mA
|
4.00 mA to 39.99 mA
|
10 μA
|
2.0% + 0.03 mA
|
40.0 mA to 399.9 mA
|
100 μA
|
2.0% + 0.3 mA
|
0.400 A to 3.999 A
|
1 mA
|
2.0% + 3 mA
|
4.00 A to 39.99 A
|
10 mA
|
2.0% + 30 mA
|
1 Applies to signal frequency
-
40 Hz to 1 kHz with filter set to OFF
-
40 Hz to 70 Hz with filter se to ON
|